Archiving and Historical Trends

Data archiving is usually an integral part of every visualization or the control system of any technological process. Data archiving means in principle storing measured or calculated variables into data files. Data archiving may of course incorporate tracking of historical trends, state changes of tracked variables, alarms or failures and also backup of important variables of the application. For each such activity there is available either a special data section, an attribute of a data element or a virtual instrument.

In the Control Web data is archived in standard databases. The data in archive files are organized as a form of tables where each individual table line represents one record and each individual column one record item. Each item of a record is identified by its name, type, and size.

Database File Structure

Database File Structure

It is possible to archive data periodically on the basis of a certain event (e.g. exceptions from the driver) or by calling of native OCL procedures. When setting the archiving parameters, it is possible to define not only the target database, but also the target table (file) and the historical availability of data, i.e. to specify the time period during which data will be stored in the database. The archived data is recorded in the file by records and in a standard manner the item with the time mark is added to each record that uniquely specifies the time of gathering the value of the archived variable.

The Control Web also offers a series of possibilities and tools for reading and processing of archived data from the databases. As has already been mentioned, data is archived in standard databases and, therefore, is available for processing also in other applications.

Archiving by using of archive data sections

The most natural, simplest, and practically a problem-free manner of archiving in the Control Web is system archiving by using of archive data sections (archive sections). Archive data sections are defined in the Data inspectors tab in the Data elements item.

Archive data section definition

Archive data section definition

Data elements located in those data sections are implicitly archived into tables with the same name as the archive section. The target database is described using the database attribute, which contains the name of the identifier referring to the parameter definition of the connection to the database. The database connection parameters are defined in the Data editor of the Database section.

If the section defines this attribute, the default database will be used for archiving data elements.

If data elements are archived into MDB (the format used by e.g. Microsoft Access), this file is always compressed before application start for reason of possible fragmentation of the database file. This operation can last even several minutes, according to the database size. If you want to prevent this activity, you can ban this operation in the system data inspector.

Remark:

Archiving in MDB database is available only in 32-bit version of the Control Web system.

Data elements in the archive section can be archived with the frequency defined within the section or in the period typed directly for the data element.

The following picture shows the definition of the Archive1 archive data section with the frequency of archiving of 5 seconds that contains four data elements.

Definition example of data elements in the archive data section

Definition example of data elements in the archive data section

Each archive data element must have a unique name within the section, which is used for identification in the archive table. In addition to the name of the data element, its value and type, the archive table also contains the time mark — UTC time in the form of Julian date, zonal time offset, and daylight saving time offset.

Example of the archive section data in the database table

Example of the archive section data in the database table

All data archived by archive sections can be browsed in the application of the Control Web by means of the data_viewer virtual instrument.

Browsing the archived data

The data_viewer instrument is used for displaying data stored by archive sections in the database files. The instrument reads the data from files and displays it in the form of a graph or table.

The data_viewer instrument can work in two modes:

  • Monitoring mode (the “online” mode).

  • Archived data browsing mode within the entire history (the “offline” mode).

Before starting an application containing the data_viewer instrument we must perform the basic setting of the instrument parameters.

Instrument Inspector data_viewer

Instrument Inspector data_viewer

  1. In the Activity section set the period parameter. This parameter specifies the time interval, in which the instrument will require data from the database.

  2. It is necessary to specify which data is to be displayed. It concerns data elements defined in some archive section. The data_viewer instrument associates data elements into logical groups and puts one of these groups into the graph or the table. During the running of the application it is possible to switch between groups. The groups are defined in the data_group parameter.

    Definition of groups

    Definition of groups

    The following parameters must be set for each group:

    • group_name — the group identifier. This is the name uniquely identifying the group. It is used e.g. for calling native procedures.

    • title — the text describing the group. It is recorded in the graph title.

    • item — the list of group data elements. Data elements are identified by the full name, i.e. the archive section name separated from the data element name by a period. At the place of the data element name, there can be wildcards conventions for names. The group name must be mentioned in apostrophes. Array data elements cannot be incorporated into the group as a whole, however, it is possible to type individual elements of the array. For each data element it is possible to type the identifier (name) of axis y axis_name, the width of the graph line line_width and the color by which the course will be drawn color. The mask parameter defines the mask for displaying numeric values of the element in the time cursor information window and in the viewer_mode = table mode. The description parameter defines the text string describing the data element in the graph legend and in the time cursor information window in the viewer_mode = chart mode.

  3. Setting parameter active_group — the name of the group that will be drawn after starting the application.

  4. Definition of the time axis of the graph. The time axis is defined in the time_axis sub-section of the chart_description section.

    Definition of the time axis

    Definition of the time axis

    For the time axis it is necessary to set the following parameters:
    • content — the time axis description content

    • text_orientation — text orientation of axis caption

    • date_time_in_line — the parameter value here defines, whether date and time captions will be written adjacently (parameter set to true) or consecutively (parameter set to false)

    • position — the time axis position

    • time_interval — the time axis length

    • begin_axis — the time axis beginning

    • granularity — defines the alignment of the beginning of the time axis to full seconds, minutes, hours or days.

    • grid_count — defines how many sections the time axis will be divided into

    • label — the name of the time axis

    • date_mask — the mask for displaying date on the time axis. If the parameter is not defined, the date is displayed in the format specified by the MS Windows setting.

    • time_mask — the mask for displaying time on the time axis. If the parameter is not defined, the time is displayed in the format specified by the MS Windows setting.

    • scales — a list containing predefined lengths of the time axis

  5. Definition of the y axis (or axes). The axis is defined in the axis_element parameter in the y_axes sub-section of the chart_description section.

    Definition of axis y

    Definition of axis y

    Parameters of axis y:
    • name — the axis identifier. This is the name uniquely identifying the axis. It is used e.g. for calling native procedures.

    • visible — defines the visibility of the axis. States whether the axis should be drawn.

    • label — the text description (title) of the axis.

    • units — the dimension of the value.

    • sheet_title — sheet title.

    • scale_type — defines the type of the axis scale. The axis scale can be logarithmic or linear.

    • number_format — the format of writing numbers in the axis label (decimal or semi-logarithmic format). The semi-logarithmic format can be written in scientific or engineering notation.

    • precision — the number of displayed decimal places in the scale description.

    • range_from — the lower limit of the scale.

    • range_to — the upper limit of the scale.

    • auto_range — enables automatic adaptation of the high_value and the low_value border of the axis according to values of displayed data elements

    • low_limit — the lower limit value

    • high_limit — the upper limit value

    • major_incr — the main step of the raster.

    • minor_incr — the minor step of the raster.

  6. Definition of the instrument mode. The viewer_mode parameter determines in which form the data will be displayed. The instrument can work in two modes:

    • chart — the data will be displayed in the form of a graph

    • table — the data will be displayed in the form of a table

  7. If in the instrument appearance definition (the content parameter) the graph title is defined, it is necessary to set its parameters. Each title may contain up to three lines of text. For each line it is possible to set a different font and color of the text. It is possible to define the title transparency, the title frame, and the background color. The title parameters are defined in the title section.

As soon as all the basic parameters are set, it is possible to run the application.

Instrument in mode chart

Instrument in mode chart

Switching between modes can be easily performed by pressing button .

Instrument in mode table

Instrument in mode table

The number of displayed values in one instrument is not restricted. When the application is running it is possible to switch between the displayed groups and to switch the display of each monitored course on or off. In the chart mode it is possible to change the displayed time interval, the number of grid lines in both the horizontal and vertical direction, the calibration and the y axis range at any time. In the “offline” mode it is possible to read values by means of the time cursor.

Summary

  • Archive data sections are used for archiving.

  • Data is stored in database files.

  • Archived data can be browsed in the application by means of the data_viewer instrument.

 